130273 - 5374-S00
Latest Information
www.biaonline.com
Catalog No. 5374-S00

Product availability

Contact our sales office to get additional information

Catalog No. : 5374-S00
EDP Number : 130273

Target Countries : USA, Canada, Mexico

Description :
Flush Mounting Receptacle, 50 Amp, 250 Volt AC, NEMA 6-50R, 2-Pole 3-Wire Grounding (2P+E), Straight Blade, Industrial Grade, Side Wired, Steel Strap, Black — WARNING: Do not use with single-gang wallboxes, single-gang mud rings or single-gang box extenders.

Country of origin : MX – MEXICO
Taric Number : 85366990
Subject to change

Brandname : Leviton

Technical Information

Logistic Informations

Standard qty. : 2480 Each
Carton quantity (VPE) : 10 Each
Shipping weight : 0.160 kg / Each
Gross volume : 0.510 m³ / 1000
Net weight : 0.117 kg / Each

AC Horsepower Ratings

At Rated Voltage : 3 HP

Electrical Specifications

Voltage : 250 VAC
Amperage : 50 A
Current Limiting : Full Rated Current
Dielectric Voltage : Withstands 2000V per UL498
Poles and Wires : 2P 3W Grounding (L+N+PE)
Temperature Rise : Max 30°C after 50 cycles OL at 150 percent rated current

Environmental Specifications

Flammability : Rated V-2 per UL 94
Operating Temperature : -40°C to +60°C

Material Specifications

Body Material : Polypropylene
Device Color : Black
Face Material : Polypropylene
Line Contacts : Brass Double-Wipe
Strap Material : Galvanized Steel

Mechanical Specifications

Socket Configuration : NEMA 6-50R
Terminal Accom. : #4 AWG
Product ID : Ratings are permanently marked on device
Terminal ID : Brass screws = Hot; Green screw = Ground

Standards and Certifications

ANSI : C73
CSA : 22.2 No 42, C22.2 No.14, C22.2 No.65
UL File : E13399
NEMA : WD-6
NOM : NOM - ANCE
UL : UL 498, UL 486E

Comments

To ensure correct and speedy wiring, terminals have ID markings.
Flush mount receptacles fit Leviton′s wide range of 2.15″-diameter wallplates and mounting hardware is included.
Built of durable thermoplastic, Leviton Power Receptacles — come equipped with heavy-gauge, double-wire copper alloy contacts.
WARNING : Do not use with single-gang wallboxes, single-gang mud rings or single-gang box extenders.

Product Dimensions

Please contact our sales office for additional product information.

Sicherheitshinweise

Nur national gültig in Deutschland / Safety notes only valid in Germany
GENERAL NOTES
Non stock products are procurement goods, can only be ordered in standard packaging quantities and have a minimum order value. The actual product may differ from the illustration shown. The information provided here is subject to change without notice. The product availability is continuously updated every 15 minutes on working days. The product shown is for the use in the specified country. If no CE reference is included in the product description, the use of this product within the European Union or the CE marking itself is not permitted. The use of non-compliant equipment within the European Union is prohibited by law.
SAFETY NOTES
Installation may only be carried by people (qualified electricians) with relevant electrical engineering knowledge and experiences!
DISPOSAL INFORMATION   Must not be disposed with household waste!
WEEE No.: DE 54087582 — Information provided in compliance with §18 paragraph 4 sentence 3 WEEE Directive available at www.bmuv.de
Specifications and information are nominal
and are subject to change without notice.